KE-N Series

KE-8KD5L1EF

IP66 Off-Grid Inverter For European Grid

Features

Features
  • 01

    Fully optimized insulation resistance detection technology

  • 05

    Optional connectivity to Ktech RSD Cloud platform

  • 02

    Dual AC input and dual AC output ports

  • 06

    Optional mixed-loading capability

  • 03

    MPPT tracking efficiency up to 99%

  • 07

    Optional AFCI (Arc Fault Circuit Interrupter) protection

  • 04

    Optional integration with Ktech iHEMS system

  • 08

    Optional 10-year warranty coverage

Model KE-8KD5L1EF KE-10KD5L1EF KE-12KD5L1EF
AC Input/Output Data
Rated AC Input/Output Active Power (W) 8000 10000 12000
Rated AC Input/Output Current (A) 33.3 41.7 50
Max. AC Input/Output Current (A) 36.7 45.8 55
Peak Power (off-grid) 2 Times Of Rated Power, 10s
Power Factor Adjustment Range 0.9 – 1
Rated Input/Output Voltage/Range (V) 220/230 0.88Un < U < 1.1Un
Rated Input/Output Grid Frequency/Range(Hz) 50/45 – 55, 60/55 – 65
Grid Connection Form L+N+PE
Total Current Harmonic Distortion THDi <3% (Rated power)
DC Current Output <0.5% x Rated current
Conversion Time (Bypass and Inverter)(ms) 10
Battery Input Data
Battery Type Lead-acid / Lithium Iron Phosphate Battery
Max.Charging Current(A) 200
Max.Discharging Current(A) 200
Battery Voltage Range(V) 40 – 60
Charging Strategy for Li-ion Battery BMS adaptivity
Number of Battery Input 1
PV String Input Data
No. of Circuits 2/2 + 2
Max. PV Open-circuit Voltage (V) 550
Start-up Voltage (V) 100
Rated PV Voltage (V) 370
MPPT Voltage Range (V) 125 – 425
Max. PV Input Power (W) 12000 15000 18000
Max. Operating PV Input Current (A) 26 + 26
Max. Input Short-Circuit Current (A) 44 + 44
Efficiency
Max. Efficiency 97.60%
Euro Efficiency 96.50%
MPPT Efficiency >99%
Equipment Protection
Integrated DC polarity reverse connection protection, AC output overload protection, thermal protection, AC output overvoltage protection, AC output short circuit protection, DC component monitoring, overvoltage load drop protection, ground current monitoring, grid monitoring, ground fault monitoring, DC input switch, DC terminal impedance monitoring, residual current monitoring (RCD), surge protection
General Data
Ingress Protection (IP) Rating IP66
Operating Temperature Range(℃) -40 – + 60, >45℃ Derating
Permissible Ambient Humidity 0 – 100%
Type of Cooling Intelligent Air Cooling
Communication Port RS485/CAN/Wi-Fi/Bluetooth/4G
Dimensions(HxWxD) 638x363x230mm
Weight 30kg
Permissible Altitude(m) <2000
Warranty 5 Years/10 Years
Certification
Overview CE-LVD EN IEC 62109-1/-2,RoHS

Related Products

contact us

*We respect your privacy. When you submit your contact information, we agree to only contact you in accordance with our Privacy Policy.